← Backflow review queue
Backflow assembly test · 3855 Orchard Way
ApprovedFiled May 7, 2026 by Rowan Benton, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- May 7, 2026
- Assembly type
- DC
- Serial number
- W533549
- Size
- 1
- Test gauge serial
- G-6444
- Gauge calibration date
- Nov 16, 2025
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-21-01097
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3855 Orchard Way
Owner: Emerson Wexler
Parcel 053-21-01097