Backflow assembly test: 3398 Laurel Ct

Approved

Filed May 11, 2023 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 11, 2023
Assembly type
DC
Serial number
W887825
Size
1
Test gauge serial
G-8828
Gauge calibration date
Oct 23, 2022
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-50-01315
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3398 Laurel Ct
Owner: Logan Lindqvist
Parcel 053-50-01315