Monterey County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Bakery

Approved

Filed Jul 28, 2025 by Cameron Kessler, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Jul 28, 2025
Assembly type
RP
Serial number
W596231
Size
1 1/2
Test gauge serial
G-9301
Gauge calibration date
Apr 6, 2024
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 053-40-01290
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4125 Hickory Ct
Owner: Harlow Holdings LLC
Parcel 053-40-01290