Monterey County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7185 Turkey Hill Rd

Approved

Filed Nov 17, 2025 by Rowan Benton, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Nov 17, 2025
Assembly type
RP
Serial number
W106991
Size
3/4
Test gauge serial
G-7064
Gauge calibration date
Aug 4, 2025
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 053-33-01272
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.