Monterey County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7185 Turkey Hill Rd

Filed Nov 24, 2026 by Cameron Kessler, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Nov 24, 2026
Assembly type
RP
Serial number
W106991
Size
3/4
Test gauge serial
G-8439
Gauge calibration date
Mar 20, 2026
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 053-33-01272
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

7185 Turkey Hill Rd
Owner: Logan Ashby
Parcel 053-33-01272