← Backflow review queue
Backflow assembly test · 7146 Pine Knoll Ct
ApprovedFiled Feb 26, 2025 by Emerson Calloway, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 26, 2025
- Assembly type
- PVB
- Serial number
- W345348
- Size
- 3/4
- Test gauge serial
- G-3982
- Gauge calibration date
- Jul 2, 2024
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-31-01136
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.