← Backflow review queue
Backflow assembly test · 1198 Old Church Trl
ApprovedFiled Aug 1, 2026 by Hayden Pruitt, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 1, 2026
- Assembly type
- RP
- Serial number
- Z150255
- Size
- 1
- Test gauge serial
- G-6196
- Gauge calibration date
- May 30, 2026
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Pruitt, current on the service date
- All required fields present
- Address matches parcel 055-23-01019
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1198 Old Church Trl
Owner: Riley Brandt
Parcel 055-23-01019