Backflow assembly test · 978 Sycamore Trl
ApprovedFiled Nov 15, 2025 by Parker Brandt, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 15, 2025
- Assembly type
- RP
- Serial number
- B908079
- Size
- 3/4
- Test gauge serial
- G-3186
- Gauge calibration date
- May 12, 2025
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-72-01178
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.