Backflow assembly test · 4703 Ridgeview Dr
ApprovedFiled May 16, 2025 by Alex Okafor, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- May 16, 2025
- Assembly type
- DC
- Serial number
- W810256
- Size
- 3/4
- Test gauge serial
- G-1792
- Gauge calibration date
- Nov 6, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Okafor, current on the service date
- All required fields present
- Address matches parcel 055-63-01215
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.