← Backflow review queue
Backflow assembly test · 766 Pine Knoll Way
Needs reviewFiled Nov 24, 2026 by Cameron Ellery, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- W397947
- Size
- 3/4
- Test gauge serial
- G-3372
- Gauge calibration date
- Apr 9, 2026
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-22-01088
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
766 Pine Knoll Way
Owner: Reese Stroud
Parcel 055-22-01088