Backflow assembly test · 4464 Turkey Hill Dr

Approved

Filed Aug 19, 2024 by Avery Ramirez, Patriot Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Aug 19, 2024
Assembly type
RP
Serial number
A435504
Size
3/4
Test gauge serial
G-4809
Gauge calibration date
Nov 3, 2023
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-86-01284
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4464 Turkey Hill Dr
Owner: Taylor Harlow
Parcel 059-86-01284