← Backflow review queue
Backflow assembly test · Main Street Self Storage
ApprovedFiled Nov 28, 2023 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 28, 2023
- Assembly type
- DC
- Serial number
- W933783
- Size
- 2
- Test gauge serial
- G-5392
- Gauge calibration date
- Oct 27, 2023
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-79-01130
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4185 Mill Creek Way
Owner: Fairley Holdings LLC
Parcel 059-79-01130