Backflow assembly test · 8607 Hickory Way
ApprovedFiled Jul 27, 2025 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jul 27, 2025
- Assembly type
- RP
- Serial number
- Z102910
- Size
- 1
- Test gauge serial
- G-6448
- Gauge calibration date
- Oct 8, 2024
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-62-01110
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.