Orange County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Grill

Approved

Filed Aug 28, 2026 by Avery Ramirez, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Aug 28, 2026
Assembly type
RP
Serial number
W787526
Size
1
Test gauge serial
G-6268
Gauge calibration date
Apr 7, 2026
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-64-01120
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5952 Mill Creek Trl
Owner: Vance Holdings LLC
Parcel 059-64-01120