← Backflow review queue
Backflow assembly test · 3734 Ridgeview Dr
ApprovedFiled May 17, 2026 by Riley Calloway, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- May 17, 2026
- Assembly type
- DC
- Serial number
- Z139465
- Size
- 3/4
- Test gauge serial
- G-3996
- Gauge calibration date
- Dec 15, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-21-01248
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3734 Ridgeview Dr
Owner: Shawn Ramirez
Parcel 059-21-01248