← Backflow review queue
Backflow assembly test · 4883 Laurel Rd
ApprovedFiled Oct 11, 2024 by Casey Pruitt, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 11, 2024
- Assembly type
- RP
- Serial number
- W325606
- Size
- 1
- Test gauge serial
- G-8496
- Gauge calibration date
- Jul 1, 2024
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-85-01020
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4883 Laurel Rd
Owner: Jamie Pruitt
Parcel 061-85-01020