← Backflow review queue
Backflow assembly test · 9490 Turkey Hill Dr
ApprovedFiled Jan 31, 2025 by Avery Calloway, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 31, 2025
- Assembly type
- PVB
- Serial number
- W239872
- Size
- 3/4
- Test gauge serial
- G-7084
- Gauge calibration date
- Nov 27, 2024
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Calloway, current on the service date
- All required fields present
- Address matches parcel 061-41-01114
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9490 Turkey Hill Dr
Owner: Quinn Vance
Parcel 061-41-01114