Backflow assembly test · 187 Meadow Lark Trl
ApprovedFiled Feb 15, 2026 by Taylor Ashby, Valley Backflow Testing · filed from phone
Report
- Date of service
- Feb 15, 2026
- Assembly type
- RP
- Serial number
- B202135
- Size
- 3/4
- Test gauge serial
- G-2174
- Gauge calibration date
- Dec 12, 2024
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-69-01236
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
187 Meadow Lark Trl
Owner: Taylor Ramirez
Parcel 061-69-01236