Backflow assembly test · Hilltop Pizza

Approved

Filed Apr 12, 2026 by Taylor Ashby, Valley Backflow Testing · filed from phone

Report

Date of service
Apr 12, 2026
Assembly type
RP
Serial number
K553336
Size
1
Test gauge serial
G-5173
Gauge calibration date
Mar 7, 2026
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 061-60-01213
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.