← Backflow review queue
Backflow assembly test · Riverside Apartments
ApprovedFiled Aug 24, 2025 by Jamie Kessler, Valley Backflow Testing · filed from phone
Report
- Date of service
- Aug 24, 2025
- Assembly type
- RP
- Serial number
- Z129874
- Size
- 4
- Test gauge serial
- G-3321
- Gauge calibration date
- Apr 1, 2025
- Check valve 1
- 5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-92-01277
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
746 Sycamore Trl
Owner: Calloway Holdings LLC
Parcel 061-92-01277