Backflow assembly test · 1174 Hickory Trl
ApprovedFiled Mar 25, 2026 by Jamie Kessler, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Mar 25, 2026
- Assembly type
- DC
- Serial number
- Z274845
- Size
- 1
- Test gauge serial
- G-1129
- Gauge calibration date
- Sep 12, 2025
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-47-01162
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.