Backflow assembly test · 6944 Laurel Rd
ApprovedFiled Jan 16, 2026 by Reese Whitcomb, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 16, 2026
- Assembly type
- PVB
- Serial number
- A602390
- Size
- 1
- Test gauge serial
- G-7044
- Gauge calibration date
- Apr 17, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 065-51-01278
- Readings in range, no flags
- Result: passing. Next due date resets when approved.