← Backflow review queue
Backflow assembly test · 4849 Laurel Rd
ApprovedFiled Apr 6, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Apr 6, 2026
- Assembly type
- RP
- Serial number
- B294269
- Size
- 1
- Test gauge serial
- G-6154
- Gauge calibration date
- Nov 30, 2025
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-69-01254
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4849 Laurel Rd
Owner: Quinn Ashby
Parcel 067-69-01254