Backflow assembly test · 6695 Quarry Dr
ApprovedFiled Jun 9, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 9, 2026
- Assembly type
- RP
- Serial number
- A749157
- Size
- 3/4
- Test gauge serial
- G-8052
- Gauge calibration date
- Jun 1, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-46-01060
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.