Backflow assembly test · 2499 Spring Branch Dr
ApprovedFiled May 20, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- May 20, 2026
- Assembly type
- RP
- Serial number
- A987812
- Size
- 1
- Test gauge serial
- G-6851
- Gauge calibration date
- Feb 12, 2026
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-97-01012
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.