Backflow assembly test · 685 Cedar Hollow Rd
ApprovedFiled Dec 19, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 19, 2024
- Assembly type
- PVB
- Serial number
- K348905
- Size
- 3/4
- Test gauge serial
- G-6787
- Gauge calibration date
- Jul 15, 2024
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-61-01126
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.