Backflow assembly test · Golden Self Storage
ApprovedFiled Feb 17, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 17, 2026
- Assembly type
- DC
- Serial number
- Z303380
- Size
- 1
- Test gauge serial
- G-6739
- Gauge calibration date
- Sep 4, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-63-01197
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8645 Ridgeview Way
Owner: Okafor Holdings LLC
Parcel 067-63-01197