← Backflow review queue
Backflow assembly test · 9102 Spring Branch Trl
Needs reviewFiled Nov 22, 2026 by Reese Danner, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 22, 2026
- Assembly type
- RP
- Serial number
- A883355
- Size
- 1
- Test gauge serial
- G-9537
- Gauge calibration date
- Jun 20, 2026
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-46-01025
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
9102 Spring Branch Trl
Owner: Cameron Marsh
Parcel 067-46-01025