Backflow assembly test · 2905 Pine Knoll Rd
ApprovedFiled Jun 26, 2024 by Blake Danner, Summit Backflow Testing · filed from phone
Report
- Date of service
- Jun 26, 2024
- Assembly type
- DC
- Serial number
- Z304672
- Size
- 1
- Test gauge serial
- G-5277
- Gauge calibration date
- Sep 10, 2023
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Danner, current on the service date
- All required fields present
- Address matches parcel 071-32-01274
- Readings in range, no flags
- Result: passing. Next due date resets when approved.