← Backflow review queue
Backflow assembly test · Hilltop Car Wash
ApprovedFiled Aug 23, 2024 by Sam Nguyen, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 23, 2024
- Assembly type
- DC
- Serial number
- Z174600
- Size
- 1 1/2
- Test gauge serial
- G-9294
- Gauge calibration date
- Mar 27, 2024
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 071-34-01182
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2942 Meadow Lark Ln
Owner: Wexler Holdings LLC
Parcel 071-34-01182