← Backflow review queue
Backflow assembly test · 7016 Sycamore Trl
ApprovedFiled Aug 31, 2026 by Blake Danner, Summit Backflow Testing · filed from phone
Report
- Date of service
- Aug 31, 2026
- Assembly type
- RP
- Serial number
- Z957074
- Size
- 1
- Test gauge serial
- G-3369
- Gauge calibration date
- Aug 22, 2025
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 071-96-01016
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7016 Sycamore Trl
Owner: Alex Nguyen
Parcel 071-96-01016