← Backflow review queue
Backflow assembly test · Golden Market
ApprovedFiled Sep 1, 2026 by Parker Fairley, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Sep 1, 2026
- Assembly type
- RP
- Serial number
- B494222
- Size
- 2
- Test gauge serial
- G-3965
- Gauge calibration date
- Dec 5, 2025
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-79-01166
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2028 Quarry Way
Owner: Wexler Holdings LLC
Parcel 073-79-01166