Backflow assembly test · 4435 Pine Knoll Trl
ApprovedFiled Feb 19, 2026 by Parker Fairley, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Feb 19, 2026
- Assembly type
- RP
- Serial number
- B113782
- Size
- 1
- Test gauge serial
- G-8607
- Gauge calibration date
- Jan 9, 2026
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-80-01127
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4435 Pine Knoll Trl
Owner: Hayden Nguyen
Parcel 073-80-01127