Backflow assembly test · 934 Mill Creek Ln
ApprovedFiled Oct 15, 2025 by Logan Vance, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 15, 2025
- Assembly type
- RP
- Serial number
- Z868673
- Size
- 1
- Test gauge serial
- G-9287
- Gauge calibration date
- Apr 30, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-47-01264
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.