Backflow assembly test · 8350 Laurel Dr
ApprovedFiled Nov 5, 2025 by Logan Vance, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 5, 2025
- Assembly type
- PVB
- Serial number
- A346502
- Size
- 3/4
- Test gauge serial
- G-5006
- Gauge calibration date
- May 8, 2025
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-82-01188
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8350 Laurel Dr
Owner: Quinn Calloway
Parcel 073-82-01188