San Diego County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Self Storage

Filed Nov 20, 2026 by Parker Okafor, Valley Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Nov 20, 2026
Assembly type
DC
Serial number
K585856
Size
4
Test gauge serial
G-5007
Gauge calibration date
Mar 21, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-18-01011
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

5943 Sycamore Rd
Owner: Ashby Holdings LLC
Parcel 073-18-01011