San Diego County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Pizza

Approved

Filed Sep 17, 2025 by Rowan Kessler, Valley Backflow Testing · filed from phone

Report

Date of service
Sep 17, 2025
Assembly type
RP
Serial number
B623069
Size
2
Test gauge serial
G-4708
Gauge calibration date
Nov 21, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-54-01218
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7121 Hickory Ln
Owner: Danner Holdings LLC
Parcel 073-54-01218