Backflow assembly test · Maple Leaf Brewing Co
ApprovedFiled Mar 26, 2025 by Jordan Wexler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 26, 2025
- Assembly type
- RP
- Serial number
- A902978
- Size
- 1 1/2
- Test gauge serial
- G-8245
- Gauge calibration date
- Jan 14, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-95-01130
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.