Backflow assembly test · 1118 Sycamore Trl
ApprovedFiled Jun 21, 2026 by Alex Wexler, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Jun 21, 2026
- Assembly type
- RP
- Serial number
- Z178100
- Size
- 1
- Test gauge serial
- G-2220
- Gauge calibration date
- Jan 29, 2026
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-65-01272
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1118 Sycamore Trl
Owner: Quinn Kessler
Parcel 075-65-01272