San Francisco County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Market

Approved

Filed Apr 1, 2026 by Alex Wexler, Heritage Backflow Testing · filed from phone

Report

Date of service
Apr 1, 2026
Assembly type
DC
Serial number
K290899
Size
4
Test gauge serial
G-9348
Gauge calibration date
Dec 8, 2025
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 075-21-01069
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9068 Sycamore Way
Owner: Calloway Holdings LLC
Parcel 075-21-01069