Backflow assembly test · Blue Heron Self Storage
ApprovedFiled Mar 10, 2025 by Alex Fairley, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Mar 10, 2025
- Assembly type
- RP
- Serial number
- A792074
- Size
- 4
- Test gauge serial
- G-3114
- Gauge calibration date
- Jan 13, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Fairley, current on the service date
- All required fields present
- Address matches parcel 077-26-01197
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4665 Spring Branch Trl
Owner: Ramirez Holdings LLC
Parcel 077-26-01197