← Backflow review queue
Backflow assembly test · 2995 Ridgeview Ct
ApprovedFiled Jun 4, 2026 by Alex Fairley, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jun 4, 2026
- Assembly type
- PVB
- Serial number
- K925399
- Size
- 1
- Test gauge serial
- G-2668
- Gauge calibration date
- Oct 6, 2025
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-50-01119
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2995 Ridgeview Ct
Owner: Taylor Ellery
Parcel 077-50-01119