Backflow assembly test · 5322 Laurel Trl
ApprovedFiled Apr 9, 2026 by Alex Fairley, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 9, 2026
- Assembly type
- RP
- Serial number
- A693171
- Size
- 3/4
- Test gauge serial
- G-1836
- Gauge calibration date
- Jul 13, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-15-01329
- Readings in range, no flags
- Result: passing. Next due date resets when approved.