ApprovedFiled Apr 23, 2026 by Parker Okafor, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 23, 2026
- Assembly type
- RP
- Serial number
- B717669
- Size
- 3/4
- Test gauge serial
- G-2910
- Gauge calibration date
- Jul 8, 2025
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-67-01209
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3915 Sycamore Way
Owner: Quinn Brandt
Parcel 079-67-01209