← Backflow review queue
Backflow assembly test · 6216 Orchard Dr
Needs reviewFiled Nov 15, 2026 by Sam Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 15, 2026
- Assembly type
- PVB
- Serial number
- Z633570
- Size
- 1
- Test gauge serial
- G-9818
- Gauge calibration date
- May 30, 2026
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-32-01072
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6216 Orchard Dr
Owner: Reese Danner
Parcel 079-32-01072