← Backflow review queue
Backflow assembly test · Station Market
ApprovedFiled May 29, 2026 by Sam Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- May 29, 2026
- Assembly type
- DC
- Serial number
- K554384
- Size
- 2
- Test gauge serial
- G-5281
- Gauge calibration date
- Feb 21, 2026
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-60-01118
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
379 Fox Run Ln
Owner: Ashby Holdings LLC
Parcel 079-60-01118