Backflow assembly test · 1280 Meadow Lark Ct
ApprovedFiled Oct 7, 2026 by Sam Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Oct 7, 2026
- Assembly type
- RP
- Serial number
- B703188
- Size
- 1
- Test gauge serial
- G-2805
- Gauge calibration date
- Jan 24, 2026
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-42-01356
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.