San Luis Obispo County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9625 Laurel Rd

Approved

Filed Dec 1, 2024 by Parker Okafor, Summit Backflow Testing · filed from phone

Report

Date of service
Dec 1, 2024
Assembly type
RP
Serial number
A674665
Size
3/4
Test gauge serial
G-7741
Gauge calibration date
Jul 31, 2023
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 079-90-01161
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

9625 Laurel Rd
Owner: Hayden Ellery
Parcel 079-90-01161