Backflow assembly test · 3622 Turkey Hill Rd
ApprovedFiled Jun 5, 2024 by Sam Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jun 5, 2024
- Assembly type
- RP
- Serial number
- B374057
- Size
- 3/4
- Test gauge serial
- G-3525
- Gauge calibration date
- Sep 12, 2023
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Vance, current on the service date
- All required fields present
- Address matches parcel 079-28-01241
- Readings in range, no flags
- Result: passing. Next due date resets when approved.