← Backflow review queue
Backflow assembly test · 3622 Turkey Hill Rd
ApprovedFiled Aug 1, 2026 by Parker Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- Aug 1, 2026
- Assembly type
- RP
- Serial number
- B374057
- Size
- 3/4
- Test gauge serial
- G-7048
- Gauge calibration date
- Feb 21, 2026
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-28-01241
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3622 Turkey Hill Rd
Owner: Casey Brandt
Parcel 079-28-01241